APC UPS Battery Backup Firmware Update Process
NMC2 APC9630 Network Card Firmware Update
- Download the .exe 7.1.6 file from APC and use
unzip name.exe
on the file to get its files. https://www.se.com/us/en/product/AP9630/apc-ups-network-management-card-2/ - If using a Windows computer or VM, just run the EXE and it will automatically do all steps of the firmware process after you put in the IP, username, and password
- Otherwise, use FTP to update https://www.apc.com/us/en/faqs/FA156047/#FTP (don't use https://www.apc.com/us/en/faqs/FAQ000242942/)
ftp ftp://apc:apc@x.x.x.x
to connect with user APC and password APC- Then
bin
to enter binary mode and thenput apc_hw05_bootmon_109.bin
. Once it uploads, disconnect withexit
and/or CTRL+C and reconnect after a couple minutes - Repeat this process twice more, firstly for
put apc_hw05_aos_716.bin
first, thenput apc_hw05_sumx_716.bin
- Modify the preconfigured config file. Update the naming everywhere else by find-and-replacing the Network Number (NN) and other similar descriptions. The MAC address can be safely ignored. Then go to Configuration/General/User Config File, pick the
nn2299-roof-apc-nmc2-config.ini
and apply it. Then reboot the NMC using Control/Network/Reboot to permanently apply the settings.
UPS Firmware Update
- These are updated way more rarely.
- Thankfully, this can be done easily through the NMC2's web UI under Configuration → Firmware upgrade. Pick the file and wait 5-10 minutes for the upgrade to
completecomplete. On older NMC2 software versions (6.x.x and earlier) the option may not be available. In that case, update the NMC2 and then update the UPS - Download the UPS firmware ZIP and find the relevant file inside. For example, a UPS with ID18 and model SMT750RM2U is going to need
SMT18UPS_15-0.enc
as per the reference table in the FAQ https://www.apc.com/us/en/faqs/FA170679/. First turn off the outlet group, which cannot be on while it's updating.